An industrial backup generator in a dim data center hall, its power cable unplugged, with an amber glow in the gap between the two connectors. The generator is ready, but the connection that should hand it the load is open.
Internet Stories

The Batteries Lasted Seven Minutes: Google Cloud's London Outage and Revolut

·9 min read

At 06:53 London time on 20 October 2026, the grid supply failed at the data center hosting one of Google Cloud's London availability zones. The batteries took the load, exactly as designed, while the diesel generators were supposed to start. They never got the order.

At 07:00 the batteries began to run out, and the servers, network switches and storage in that zone went dark. About seven minutes of margin, spent waiting for a handover that never came.

For customers of Revolut, the digital bank, none of this looked like electricity. It looked like a declined card, a transfer that would not go through, an app that would not answer.

Contents

Two incidents, one morning

The outage is really two stories stacked on top of each other. The first is physical: a building loses power, and its protection does not finish its job. Seen from outside, both begin the same way: a page that will not load. The first thing to do is check if a site is down right now, for everyone or only for you.

A power pylon under a stormy evening sky feeds amber-lit cables into a switchgear cabinet, which carries the power on as blue lines to the server racks inside the data center
The first story is physical: power from the grid to the servers. AI-generated illustration.

The second is distributed. The systems that stayed up absorb a surge of redirected work while still depending, in places, on components that have just disappeared. That second story is the one that matters to anyone who runs a website, whatever its size, and it belongs on the same shelf as the famous website crashes that started from something small.

The backup that never took over

Google's preliminary incident report, published on 22 October, describes the sequence plainly. The UPS battery banks carried the facility while the on-site emergency generators started up. Then the Programmable Logic Controller automation, "both primary and backup PLCs", failed to start the generators and transfer the load to them.

A large UPS battery cabinet in a dim data center hall, with amber indicators lit on one bank of batteries
UPS batteries can only bridge the gap until the generators take over. AI-generated illustration.

A PLC is the industrial computer that runs physical machinery. So this is not a story about two broken engines. The generators were there; the logic that should have started them and moved the load across did not run, on the main controller or on its spare.

According to the report, once the grid supply was back, engineers restored a stable utility feed, then reset and tested the generator automation controllers to restore facility power. Uptime Institute adds that Google later clarified the building was a third-party colocation facility, not a Google-owned data center.

The report is preliminary, and the cause of the controller fault is not known yet. The shape of the failure is already clear, though: owning a backup is not the same as having a handover that works.

Enjoying this article?

SonarOps checks your site and tells you where it broke. The Free plan is €0 and needs no card: 5 monitors, checked every 5 minutes.

Start free →

How one zone reached the whole region

London is the region Google calls europe-west2, made up of three availability zones. The power loss was confined to one of them, europe-west2-b.

Yet the report says customers in europe-west2-a and europe-west2-c also saw "unexpected impact", and it names BigQuery, Looker, Compute Engine, Kubernetes Engine, Regional Persistent Disk and Cloud SQL among the products affected that way.

Streams of blue light running from one cluster of server racks to another, as work is redirected to the racks still running
Failover moves the load to the zones that survived, and they have to carry it. AI-generated illustration.

Google gives two reasons. The first is capacity: failover did its job, and the sudden flood of redirected queries, database failovers and workloads saturated compute in the surviving zones. The second is dependencies: control-plane calls from regional services to metadata and catalog components in the dark zone timed out, so jobs stalled and APIs returned intermittent 500 and 503 errors.

Failover is not the villain here. It moves the load, and the dependencies, somewhere else, and that somewhere has to be able to carry both. A region with three zones can still contain one zone that everything quietly needs.

The status page was two and a half hours behind

This is the detail I keep coming back to, because I build monitoring for a living. According to the report, Google's own probers detected the problem at 07:08 BST, eight minutes in.

A dark operations room overlooking a server hall: racks marked with red crosses on one side, traffic flowing to healthy racks on the other, and the same picture on the monitors
Inside, the failure showed up within minutes. AI-generated illustration.

The first entry on Google's public Service Health page is timestamped 08:35 UTC. That is 09:35 in London: two hours and thirty-five minutes after the incident began.

I don't read that as negligence. A status page is written by people, and people wait until they know what to say. But it means a provider's status page is a communication tool, not an alarm.

If your plan for a provider outage is to watch their status page, you have planned to find out late.

The cloud recovered before the bank

By 13:10 BST, Google says, availability had recovered for the vast majority of customer workloads, and over 99% of Compute Engine virtual machines were healthy. That closes the official window: 07:00 to 13:10, six hours and ten minutes. A final notice followed at 15:03, after a small tail of isolated workloads recovered.

Revolut's day was longer. At 17:00 GMT (18:00 in London), Reuters reported that only six of the 27 services on Revolut's UK website were listed as working, among them support chat and internal transfers. Card payments, transfers, ATM withdrawals, currency exchange and stock trading were still marked as having problems.

A quiet control room at sunset, with a world map of network links on the wall and dashboards showing mostly green
By early afternoon the platform was mostly green again. AI-generated illustration.

Revolut said its customers' money and data were safe. By 18:52 BST at the latest, BleepingComputer was quoting the company: "The issue has now been fixed, and services are now restored."

Two cautions before reading too much into those numbers. Other outlets counted 28 and 31 affected services at other moments of the day, so "6 of 27" is a snapshot, not a metric. And the two timelines measure different things: cloud workloads on one side, banking features on the other.

Without a technical write-up from Revolut, any explanation of the extra hours (queues, reconciliation, application dependencies) would be a guess, so I won't make one. What the numbers show is enough: a provider declaring recovery is not the same as your product working again.

Redundancy is not independence

I learned this one on my own infrastructure. During a failover drill in July, I powered off my production primary for real. The automation did everything right: the standby was promoted, DNS moved across, the health check went green.

The site returned a 521 error for the entire window. The standby had the data, but not the front door: no web server, no TLS certificate, nothing to answer a browser. I wrote the whole drill up in I Shut Down My Production Database on Purpose.

It is the London lesson at a much smaller scale. A copy of something is only a backup if the path to using it has been exercised.

The same test applies to any setup labelled "highly available". Two replicas behind one shared dependency are not independent against that dependency, which is the same pattern as the single points of failure that hold up the internet. A surviving zone without spare capacity is up, and still slow.

Architectures deserve to be judged by how they fail, not by how many copies they advertise.

What an outside monitor can and cannot see

An external uptime check looks at a service the way a visitor does: from outside the provider. It can see a wrong HTTP status, a timeout, or a response that suddenly takes ten times longer than usual. That outside view matters most when the internal dashboards are green and real requests are still failing.

That outside view is what SonarOps uptime monitoring gives you, and it does not alert on the first failed check. The same probe retries after a couple of seconds; if the check still fails, a second probe in a different data center tries; if that fails too, the first probe usually checks once more about 30 seconds later before an incident opens.

A failure that keeps repeating on the regular checks opens an incident anyway. The price of the sequence is a short delay; what it buys is fewer alerts caused by one bad network path. The whole path from failed check to alert is described in incident detection.

An HTTP 200 on a login page proves very little about a bank, though. It does not prove that a card payment clears or that a transfer settles. Those journeys need application telemetry and synthetic tests built so that they never move real money.

Uptime monitoring is the outer layer, not a certificate of health.

Lessons for people who run websites

An agency looking after thirty WordPress sites, or a seasonal online shop, does not need a bank's architecture. It can borrow the method:

  • Separate your provider's health from what your users can actually do.
  • List your shared dependencies, including the boring ones: DNS, authentication, the control plane you never think about.
  • Check that wherever your failover lands has room for the extra load.
  • Drill the handover, not just the standby. Watch it work at least once.
  • Monitor public endpoints and critical user journeys separately.
  • Report status per function, as available, degraded or unavailable, on a status page of your own. One green light hides too much.

Each item needs an owner, a signal you can measure and a recovery procedure written down before the day you need it.

The handover is the backup

In London the generators were on site. So were the controllers, two of them. What failed was the moment in between: the seven minutes in which one system had to hand the load to another.

A backup is not something you own. It is a handover you have watched work.

Sources and references

  1. Google Cloud. "Preliminary Incident Report", Google Cloud Service Health, 22 October 2026 (incident Xs2XTHzAVC9YnafnPyzj). Google Cloud Service Health.
  2. Reuters. "Revolut says some services back online after outage", 20 October 2026. Reuters via MarketScreener.
  3. Reuters. "Google Cloud outage in UK eases after impacting digital banks, public sector websites", 20 October 2026. Reuters via Euronext.
  4. Dr. Owen Rogers, Uptime Institute. "Google UK outage: who is responsible when cloud apps fail?", October 2026. Uptime Intelligence.
  5. Sergiu Gatlan, BleepingComputer. "Revolut outage disrupts online banking operations worldwide", 20 October 2026 (update of 13:52 EDT). BleepingComputer.